Velleman DVM52IT Specifiche Pagina 3

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 32
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 2
DVM52IT VELLEMAN
3
5.1 General Specifications
Max. voltage between terminals and earth 1000V dc or ac
Measuring Method Dual-slope integration A/D converter
Sampling Time ±0.4sec.
LCD Height 22mm
Max. Display 1999 points (3 ½ digits)
Polarity Indication ‘-‘ indicates negative polarity
Overrange Indication ‘1’ or ‘-1’ is displayed
Displayed Measuring Unit Unit of electrical capacity
Power Supply 6 AA-batteries of 1.5V (alkaline batteries are recommended)
Power Consumption ±5mA (100Vdc, 750Vac, 200, )
±30mA (200M, 250V)
±50mA (200M/500V)
±100mA (2000M/1000V)
Battery-Low Indication ”-symbol is displayed
Operating Temperature 0 to 40°C (32 to 104°F)
Operating Humidity < 85%RH
Storage Temperature -10 to +50°C (10 to 122°F)
Dimensions 192 x 122 x 55mm
Weight ± 545g (with batteries)
5.2 Electrical Specifications
5.2.1. Insulation Resistance
Range
200M
/ 250V 200M
/ 500V 2000M
/ 1000V
Test Voltage 250Vdc ± 10% 500Vdc ± 10% 1000Vdc ± 10%
0 ~2000M
Measuring Ranges
0 ~200M 0 ~200M
0 ~1000M 1000 ~2000M
Accuracy ± 3% rdg ± 5 digits ± 5% rdg ± 5 digits
Output Voltage on Open Circuit 250V ± 10% 500V ± 10% 1000V ± 10%
Min. Output Voltage
225V at 0.25M 450V at 0.5M 900V at 1M
Test Current (approx.)
1mA at 0.25M 1mA at 0.5M 1mA at 1M
Output Short-Circuit Current
2.5mA
5.2.2. AC Voltage
Range Resolution Accuracy
700V 1V ±1.2% of rdg + 5 digits
Input Impedance 10M
Max. Input Voltage 700V rms AC or 1000V DC
Frequency Range 40 to 400Hz
Response average, calibrated in rms of a sine wave
Vedere la pagina 2